Classrooms and other school spaces must be ventilated to remove odors and pollutants.

A typical classroom using a dedicated outdoor air system (DOAS) distributes outside air (OA) to the rooms through a dedicated diffuser or introduced through the return air duct of the sensible cooling system.

To absorb internal latent loads properly designers must design the DOAS to deliver air at a lower dew point than the required dew point condition. The dry supply air will help absorb additional internal moisture, keeping the space at desired dew point conditions and preventing moisture-related problems.

Typically, engineers wanting to use a DOAS best design practice (divide and conquer), would plan to use a system that would deliver OA at a "neutral" condition, 75°F/24°C and 55°F/13°C dew point. This delivered condition is commonly associated with maintaining 75°F/24°C and 50% RH.

A simple DOAS can accomplish these conditions during the cooling season by processing OA through a cold coil down to a 55°F/13°C saturated condition and then reheating the air back up to 75°F/24°C, ensuring the air be delivered at 55°F/13° dew point. However, introducing OA at a 55°F/13°C dew point will not hold the space at 50% RH. A classroom will generate its own additional moisture from the students, space processes (such as in a lab), and infiltration. Schools that mop or steam clean carpets on a regular basis will introduce an incredible amount of additional moisture to the space. All of this additional moisture must be removed from the space in order to control RH within the recommended 40-60% range. Without this moisture control, structural damage and occupant health risks can happen.

  • Wij kunnen u helpen met

    Condensatie

    Wanneer water verdampt vormt zich waterdamp. Als deze waterdamp in aanraking komt met koude oppervlakken, drupt condensatie van muren, plafonds, leidingen en producten.

    lees meer

    Schimmel en bacteriën

    Een te hoog relatief vochtigheidsgehalte is de oorzaak van vele problemen in ons dagelijks leven. Van grondstoffen, productie, verpakking tot transport en opslag.

    lees meer

    Luchtkwaliteit (Comfort)

    De Indoor Air Quality (IAQ) (kwaliteit van de lucht binnen) wordt aangetast door verontreinigingen zoals stof, pollen, schimmels, meeldauw en vluchtige organische stoffen (VOS).

    lees meer
  • Expertisegebieden

  • Verwante producten

    • Desiccant Dehumidification System DDS

      Basic desiccant dehumidifiers or custom total environmental control…

      Bekijk meer

      DryCool® ERV

      The Munters DryCool® ERV product combines the benefits of desiccant…

      Bekijk meer

      DryCool® Standard

      Primarily designed to be a dedicated outdoor air unit delivering space…

      Bekijk meer
    • alles weergeven

Wij zijn experts

Wij kennen onze producten. We zullen uw contact informatie aan iemand in uw land doorsturen.