Free heat from an incinerator

At a large midwestern printing plant, solvents used in ink from presses generate harmful vapors. Two regenerative thermal oxidizers, with a combined 70,000 CFM exhaust, incinerate the VOCs. But rather than let all that heat go to waste up a stack, the company wisely uses it to heat its facility.

Two Munters Thermo-Z® air-to-air heat exchangers, one on each incinerator, capture the exhaust heat and use it to heat outside air for plant makeup air in winter. Each heat exchanger is part of a complete packaged heat recovery system that also includes supply and exhaust fans, dampers, and filters.

Under design conditions, the systems heat outdoor air from -10°F to 130°F using 250°F exhaust from one incinerator and 350°F exhaust from the other. Combined, they can transfer over 10,400,000 BTUs per hour. The temperature to the space is controlled to a consistent 130°F by modulating the hot gas flow through the heat exchanger. Munters air-to-air heat recovery system successfully helped the printing plant recycle energy and save on costs.

Schnelle Fakten

  • Provides free heat, eliminating building heat costs
  • Energy savings of $250,000 annually
  • Eliminates negative pressure problems
  • One-year payback

Wie können wir Ihnen helfen?

Bitte leiten Sie mich zur allgemeinen Startseite weiter.
Durch Ihre Auswahl stimmen Sie unseren Cookie-Richtlinien zu

Ungültige Benutzerkennung

Es ist ein Fehler ist aufgetreten! Bitte versuchen Sie es später noch einmal.

Ungültige Benutzerkennung

Es ist ein Fehler ist aufgetreten! Bitte versuchen Sie es später noch einmal.